6.1 General wiring guidelines
6 Commissioning
66000CommissioningCommissioning6-6.1General wiring guidelines6100General wiring guidelines6-Verdrahtung_PNOZ mc2p
The wiring is defined in the circuit diagram of the PNOZmulti Configura-
tor.
It is possible to define which inputs and outputs on the safety system will
communicate with EtherCAT.
Note:
Information given in the "Technical details" must be followed.
Use copper wire that can withstand 75 °C.
Please note the following when connecting to EtherCAT:
The following minimum requirements of the connection cable and
connector must be met:
– Only use standard industrial Ethernet cable and connectors.
– Only use double-shielded twisted pair cable and shielded RJ45
connectors (industrial connectors).
– 100BaseTX cable in accordance with the Ethernet standard (min.
Category 5)
Measures to protect against interference:
Ensure the requirements for the industrial use of EtherCAT are met,
as stated in the Installation Manual published by the User Group.
Verdrahtung_multi_Achtung_Kabel_spannungsl_ziehen_Modul
CAUTION!
Only connect and disconnect the expansion module when the
supply voltage is switched off.