Technical details
Operating Manual PNOZ mm0p-T
1002704-EN-01
25
Mechanical data 772010
Stripping length 9 mm
Dimensions
Height 100,0 mm
Width 45,0 mm
Depth 120,0 mm
Weight 230 g
The standards current on 2012-07 apply.
Safety characteristic data
Unit Operating
mode
EN ISO
13849-1: 2006
PL
EN ISO
13849-1: 2006
Category
EN IEC 62061
SIL CL
PFH [1/h] EN ISO
13849-1: 2006
TM [year]
Logic
CPU – PL e Cat. 4 SIL CL 3 1,54E-09 20
Input
SC inputs 1-channel PL d Cat. 2 SIL CL 2 3,95E-09 20
SC inputs 2-channel PL e Cat. 4 SIL CL 3 4,61E-10 20
SC inputs 1-ch., pulsed
light beam
device
PL e Cat. 4 SIL CL 3 3,95E-10 20
Output
SC outputs 1-channel
with ad-
vanced fault
detection
PL e Cat. 4 SIL CL 3 7,65E-10 20
SC outputs 1-channel PL d Cat. 2 SIL CL 2 8,90E-10 20
SC outputs 2-channel PL e Cat. 4 SIL CL 3 7,86E-10 20
All the units used with a safety function must be considered wehn calculating the safety
characteristic data.
Information
A safety function´s SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function´s SIL/PL values.
8.1