7.1 Messages
7 Operation
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
7-2
FAULT Application Watchdog Timeout
1 Hz Configuration error, length of input and/or output data during initialisation of the PNOZ
mmc3p does not match the configuration
Remedy:
Ensure that the right GSD-file has been used.
2 Hz Configuration error, length/contents of configuration data during initialisation of the
PNOZ mmc3p does not match the configuration
Remedy:
Ensure that the right GSD-file has been used.
4 Hz Error when initialising PROFIBUS-DP
No error
LED Meaning