8.2 Service life graph of output relays
8 Technical details
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
8-4
8.2Service life graph of output relays8200Service life graph of output relays8-Lebensdauerkurve_Relais_Text vor Kurve
The service life graphs indicate the number of cycles from which failures
due to wear must be expected. The wear is mainly caused by the elec-
trical load; the mechanical load is negligible.
Lebensdauerkurve SI S_212
Lebensdauerkurve_Relais_Text nach Kurve_SIS212_SIR-SLR Bsp
Example
Inductive load: 0.2 A
Utilisation category: AC15
Contact service life: 1 000 000 cycles
Provided the application requires fewer than 1 000 000 cycles, the PFH
value (see technical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provid-
ed on all output contacts. With capacitive loads, any power surges that
occur must be noted. With contactors, use freewheel diodes for spark
suppression.
Lebensdauerkurve_Relais_Text nach Kurve-2_ Empfehlung sichere Halbleiterausgänge
We recommend you use semiconductor outputs to switch 24 VDC
loads.